Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T09CM03271
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/01/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* 1) OFFICE FURNITURE CONNECTIONS AND RACEWAY OPEN BEHIND FURNITURE 2) RECEIVED FOR CLASSIFICATION |
|
03/11/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) WAITING ON OFFICE FURNITURE AND ENGINEERS CLASSIFICATION |
|
03/02/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NEED TO SEE OFFICE FURNITURE CONNECTION 2) SUPPORT VDV OFF OF GRID PER 725.24, 300.24 AND 300.11 3) HAVE ENGINEER DEFINE CLASSIFIED AREA PER 513.3 (C) 4) FINISH VDV |
|
02/25/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) STOCK ROOM, OFFICE AND ALL CEILINGS ALL OK |
|
02/02/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) RIDGIDLY SUPPORT BOXES IN WALLS 2) PROVIDE LETTER AUTHORIZING USE OF SING GANG CUT IN BOXES 3) OK WALL AFTER CORRECTIONS |