Permit: T09CM03271

Parcel: 14043011A


Addresses:

6901 S PARK AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM03271

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/01/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
1) OFFICE FURNITURE CONNECTIONS AND RACEWAY OPEN BEHIND FURNITURE
2) RECEIVED FOR CLASSIFICATION
03/11/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WAITING ON OFFICE FURNITURE AND ENGINEERS CLASSIFICATION
03/02/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NEED TO SEE OFFICE FURNITURE CONNECTION
2) SUPPORT VDV OFF OF GRID PER 725.24, 300.24 AND 300.11
3) HAVE ENGINEER DEFINE CLASSIFIED AREA PER 513.3 (C)
4) FINISH VDV
02/25/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) STOCK ROOM, OFFICE AND ALL CEILINGS ALL OK
02/02/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) RIDGIDLY SUPPORT BOXES IN WALLS
2) PROVIDE LETTER AUTHORIZING USE OF SING GANG CUT IN BOXES
3) OK WALL AFTER CORRECTIONS