Permit: T09CM03267

Parcel: 12112404E


Addresses:

1635 N CRAYCROFT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM03267

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/08/2010 ELECTRIC - FINAL Approved Wiring is in substiantal, if not full, compliance with 408.3.
10/07/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OTHER ITEMS TAKEN CARE OF-BLDG OFFICIAL TO DETERMINE PER APPEAL SUBMITTED #1 408.3
09/30/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) VERIFY CONTINUITY OF WATER SERVICE GROUNDING ELECTRODE
2) FINISH #1,2,3 & 6
09/24/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDUCTORS TO ENTER SECTION SERVED 408.3
2) #4 TO BE TO BLDG STEEL NOT JUST A SUPPORT POST
3) GROUND LUGS HAVE FULL SURFACE CONTACT
4) MOUNT TRANSFORMER PER DETAIL
5) FUSES NOT PER PLANS
6) USE APPROVED GROUND BAR FOR DISCONNECT
7) FILL UNUSED OPENINGS AT CHILLER SWITCH
8) TIGHTEN LOOSE FITTINGS
09/13/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER CONTRACTOR
09/08/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*