Permit: T09CM03252

Parcel: 12801005H

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/12/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/11/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) DUCT SMOKE DETECTOR TEST OK
2) CONDENSATE CANNOT BE REDUCED IN SIZE
3) LABEL A/C UNIT PER MALL REQUIREMENTS
4) AIR BALANCE OK
5) MAX FUSE SIZE FOR A/C UNIT 25 AMP