Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09CM03235
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/14/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
01/08/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 4090 ITEMS 2 THRU 5 HAVE BEEN CORRECTED. PROVIDE R-8 IN ATTIC AND SHEET METAL COVER ON DUCT ON ROOF 3090 ITEMS 1 & 3 HAVE BEEN CORRECTED PROVIDE PAN UNDER W/N |
|
12/30/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : 1. ALL DUCT EXPOSED TO EXTERIOR IS TO BE INSULATED TO A MINIMUM OF R8 (2") PER 2006 IECC 2. PROVIDE APPROVED CONNECTION ON LINE VOLTAGE CONDUIT. 3. CONDENSATE IS TO TERMINATE WITHIN 6" OF GRADE. 4. ALL PVC PIPE EXPOSED TO EXTERIOR TO BE PAINTED AND BLOCKED UP OFF OF ROOF A MINIMUM OF 1.5" 5. PROVIDE UNIT DATA PLATE |