Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T09CM03211
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2010 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/22/2010 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VERIFY ACOUSTICAL INSULATION IN CURBS PER DETAIL 101 2) VERIFY FLEX CONNECTORS IN DUCT DROPS PER DETAIL 101 3) REMOVE TAPE AND SEAL ALL JOINTS WITH SEALER PER SPECS 4) MAX FLEX DUCT LENGTH IS 8' 5) PROVIDE 125 PERCENT CONICAL FITTINGS PER DETAILS 6) DUCT RIGID AND FLEXIBLE TO BE HUNG WITH S.M. STRAPS ONLY NO WIRE |