Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/08/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 02/18/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE WRITTEN APPROVAL ON INSULATION CHANGES FROM ENGINEER PRIOR TO FINAL 2) OK FOR TILES |
|
| 02/16/2010 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE BEADED COLLARS ON ALL FLEX CONNECTIONS 2) PROVIDE APPROVED INSULATION ON DUCT 3) PROVIDE SEISMIC RESTRAINTS ON ALL REGISTERS IN T-BAR CEILING 4) ITEMS DATED 2/9/10 HAVE BEEN CORRECTED |
|
| 02/03/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUSPENDED ROUGH DUCT-SEAL JOINTS |