Permit: T09CM03199

Parcel: 136244500

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
03/08/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
02/18/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE WRITTEN APPROVAL ON INSULATION CHANGES FROM ENGINEER PRIOR TO FINAL
2) OK FOR TILES
02/16/2010 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE BEADED COLLARS ON ALL FLEX CONNECTIONS
2) PROVIDE APPROVED INSULATION ON DUCT
3) PROVIDE SEISMIC RESTRAINTS ON ALL REGISTERS IN T-BAR CEILING
4) ITEMS DATED 2/9/10 HAVE BEEN CORRECTED
02/03/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUSPENDED ROUGH DUCT-SEAL JOINTS