Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
02/23/2010 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
1) STEP UP CONDENSATE TO 1" AT 1ST TEE
2) INSULATE RETURN AIR TEE
3) LEFT GAS CARD
4) PROVIDE ACCESS TO FIRE DAMPERS AND INSTALL FIRE DAMPERS PER INSTRUCTIONS
02/09/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) THIS ATTIC SPACE CANNOT BE USED AS A PLENIUM FOR RETURN AIR CONTAINING WOOD OR ANY OTHER COMBUSTIBLES
2) THE ATTIC INSULATION IS NOT PLENIUM RATED
3) REVISE PLANS IF ADDING A DUCTED RETURN AIR SYSTEM
4) DUCT SMOKE DETECTORS NOT REQUIRED BY CODE
02/04/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO SHEETROCK RESTROOMS