Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T09CM03199
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2010 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) STEP UP CONDENSATE TO 1" AT 1ST TEE 2) INSULATE RETURN AIR TEE 3) LEFT GAS CARD 4) PROVIDE ACCESS TO FIRE DAMPERS AND INSTALL FIRE DAMPERS PER INSTRUCTIONS |
|
02/09/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) THIS ATTIC SPACE CANNOT BE USED AS A PLENIUM FOR RETURN AIR CONTAINING WOOD OR ANY OTHER COMBUSTIBLES 2) THE ATTIC INSULATION IS NOT PLENIUM RATED 3) REVISE PLANS IF ADDING A DUCTED RETURN AIR SYSTEM 4) DUCT SMOKE DETECTORS NOT REQUIRED BY CODE |
|
02/04/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO SHEETROCK RESTROOMS |