Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/17/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/01/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
| 01/29/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NEED ELECTRICIAN PRESENT TO ACCESS ELECTRIC 2) REVISE PANEL DIRECTORIES 3) RECEPTS FOR HANDI CAP DOOR NOT ON PLANS 4) INSTALL RECEPT COVER PER 406.4 5) EXIT LIGHTS DO NOT APPEAR TO BE WORKING PROPERLY 6) BOXES MORE THAN 1/4" AT NEW DEVICES 314.20 FLUSH AT COMBUSTIBLES 7) COVER PLATE MISSING EXPOSED CONDUCTORS-2ND FLOOR: COMPUTER ROOM, EXIT DOOR TO HALL-3RD FLOOR: OUTSIDE KITCHEN, LARGE ROOM, SMALL ROOMS AND HALL 8) 3RD FLOOR ELECTRIC ROOM BOX OVER FILLED FOR LIGHTS |