Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T09CM03180
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2012 | FIRE - FINAL | Approved | ||
| 07/18/2012 | FIRE - FINAL | Denied | 1. DOOR IS NOT ABLE TO BE LOCKED IN ITS CURRENT STATE. | |
| 07/09/2012 | FIRE - FINAL | Cancelled | IVRS - RI canceled | |
| 06/05/2012 | FIRE - FINAL | Denied | In the approved plans occupant load of 28 is showing in the staging area, but load exiting out of Lowes main building was not calculated in so need to show the occupant load from main building into staging area both staging and main exiting might total over 49 therefore will need two exits out of staging area. Large swing gates on eastside do not meet man gate requirements as they will be locked to keep public from getting in need to remove exit signs from gates. Can not hamper the approved exiting requirements for the two preexisting exit doors from the Lowes building. |