Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T09CM03178

Parcel: 117120220


Addresses:

61 E CONGRESS ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/02/2010 MECHANICAL - FINAL Approved AEROCOOL CONTRACTING MADE FINAL REPAIRS AND RE-BALANCED SYSTEM. CONTRACTOR REPORT ACCEPTED.
03/26/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE APPROVED ROOF ACCESS (LADDER)
2) PROVIDE SMOKE FOR DUCT SMOKE DETECTOR TEST
02/16/2010 MECHANICAL - FINAL Partial Approval AIR BALANCE REPORT ACCEPTED.
12/29/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PROPER SUN SHIELDS ON FLEX CONNECTIONS
2) UNIT DATA PLATES NOT PROPERLY IDENTIFIED
3) UNITS NOT LABELED
4) HEAT PUMP HAS NO OSA INLET
5) GAS PACK UNITS HAVE NO FILTERS ON OSA INLETS
6) OSA INLETS HAVE NO MEANS OF ADJUSTMENT
7) ITEMS 5,6,7 AND 11 DATED 12/24/09 NOT COMPLETE
8) PROVIDE AIR BALANCE REPORT
9) PROVIDE DUCT SMOKE DETECTOR IN 12 TON UNIT
12/24/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSATE NOT COMPLETE
2) LOW VOLTAGE NOT COMPLETE
3) RTU NOT PROPERLY FIT ON CURB
4) RTU OUT OF LEVEL ON CURB
5) ROOF TOP DUCT NOT SEALED
6) OUTSIDE AIR INLETS NOT INSTALLED
7) DUCT NOT PROPERLY ATTACHED TO ROOF JACK
8) LINE VOLTAGE TO RTU'S NOT COMPLETE
9) GAS PIPING CONNECTIONS TO RTU'S NOT COMPLETE
10) CURBS NOT COMPLETE
11) ALL ROOF JACK/PENETRATIONS NEED TO BE DRIED IN
12) WASTE VENTS MUST BE 10' AWAY FROM OUTSIDE AIR INLETS WHEN INSTALLED (SEE REAR UNIT)