Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2010 | MECHANICAL - FINAL | Approved | AEROCOOL CONTRACTING MADE FINAL REPAIRS AND RE-BALANCED SYSTEM. CONTRACTOR REPORT ACCEPTED. | |
| 03/26/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE APPROVED ROOF ACCESS (LADDER) 2) PROVIDE SMOKE FOR DUCT SMOKE DETECTOR TEST |
|
| 02/16/2010 | MECHANICAL - FINAL | Partial Approval | AIR BALANCE REPORT ACCEPTED. | |
| 12/29/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE PROPER SUN SHIELDS ON FLEX CONNECTIONS 2) UNIT DATA PLATES NOT PROPERLY IDENTIFIED 3) UNITS NOT LABELED 4) HEAT PUMP HAS NO OSA INLET 5) GAS PACK UNITS HAVE NO FILTERS ON OSA INLETS 6) OSA INLETS HAVE NO MEANS OF ADJUSTMENT 7) ITEMS 5,6,7 AND 11 DATED 12/24/09 NOT COMPLETE 8) PROVIDE AIR BALANCE REPORT 9) PROVIDE DUCT SMOKE DETECTOR IN 12 TON UNIT |
|
| 12/24/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE NOT COMPLETE 2) LOW VOLTAGE NOT COMPLETE 3) RTU NOT PROPERLY FIT ON CURB 4) RTU OUT OF LEVEL ON CURB 5) ROOF TOP DUCT NOT SEALED 6) OUTSIDE AIR INLETS NOT INSTALLED 7) DUCT NOT PROPERLY ATTACHED TO ROOF JACK 8) LINE VOLTAGE TO RTU'S NOT COMPLETE 9) GAS PIPING CONNECTIONS TO RTU'S NOT COMPLETE 10) CURBS NOT COMPLETE 11) ALL ROOF JACK/PENETRATIONS NEED TO BE DRIED IN 12) WASTE VENTS MUST BE 10' AWAY FROM OUTSIDE AIR INLETS WHEN INSTALLED (SEE REAR UNIT) |