Permit: T09CM03176

Parcel: 13707034B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/20/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK ELECTRIC
2) ROOF GFCI MAY NOT WORK PROPERLY
01/19/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) GROUNDING EQUIPMENT CONDUCTOR TO A/C UNDERSIZED
2) FITTINGS LOOSE
3) MAINTENANCE RECEPT NOT WORKING AND TO BE GFCI PROTECTED
4) LABEL DISCONNECT
01/14/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE OR MORE THAN 1/8" AROUND 314.20 AND 314.21
2) PLEASE PROVIDE ACCESS TO ROOF TO INSPECT
01/11/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*