Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
| 01/14/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CONDUCTORS TO BE SIZED FOR FUSE AMPACITY 2) FILL UNUSED OPENINGS 3) ONLY ONE CONDUCTOR PER TERMINAL SCREW 4) CONNECT GROUNDS TO CIRCUIT EQUIPMENT GROUND 5) FINISH 2, 4 AND 6 FROM PREVIOUS INSPECTIONS |
|
| 01/11/2010 | ELECTRIC - FINAL | Partial Approval | WAITING ON COOLER BOX | |
| 01/11/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOX OVERFILLED 2) USE APPROVED CONNECTORS FOR M/C-ALSO M/C TO TERMINATE 3) SUPPORT M/C CABLE WITHIN 12" OF BOXES 4) ONY ONE CONDUCTOR PER LUG 110.14 5) MAINTAIN WORKING CLEARANCES IN FRONT OF DISCONNECTS 110.26 6) SEAL RACEWAYS ENTERING WALK IN PER 300.7 7) DISCONNECT SWITCH INSIDE BOX TO BE ENVIROMENT |
|
| 12/24/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" BOX TO SURFACE 2) EM AND EXIT LIGHTING NOT WORKING WAREHOUSES |