Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/28/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 09/16/2010 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/04/2010 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSULATION HAS VOIDS AND IS COMING APART, SEAL ALL JOINTS AND PROVIDE PROTECTION FROM SUN EXPOSURE 2) BLOCKING TO BE MASTIC TO ROOF TO PREVENT MONUMENT 3) ALL POTABLE PIPING ON ROOF TO BE INSULATED TO PREVENT FREEZING 4) FAILURE TO COMPLY HAS RESULTED IN ADDITIONAL REFEES |
|
| 04/29/2010 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* APPROVED PLAN + PERMIT NOT ON SITE MAKE ALL CORRECTIONS ON THIS INSPECTION SHEET LISTED FROM 12/21/09. THE GROUND WIRE IS NOT ATTACHED TO THE HEATER. CONTRACTOR TO PAY REINSPECTION FEE PRIOR TO FINAL INSPECTION. HAVE PETITION OF APPEAL FILLED OUT BY OWNER THAT WAS LOFT ON SITE. |
|
| 04/26/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/21/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE CORRECT COLOR WIRES FOR BOTH 110 VOLT AND 220 VOCT CIRCUITS THAT ARE NEW CIRCUITS 2) SECURE AND SUPPORT TUBING PROPERLY IN WATER HEATER CLOSET 3) DISCONNECT FOR WATER HEATER REQUIRES CORRECT CLEARANCE PER 2006 NEC 4) INSTALL TEMPERING VALVE PER PLAN 5) LOW VOLTAGE SENSOR WIRE TO BE PROTECTED ON ROOF |