Permit: T09CM03149

Parcel: 126111280


Addresses:

4404 E ELMWOOD ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/17/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
08/04/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE 2 POLE 30 AMP BREAKER FOR 220 VOLT CIRCUIT
2) PROVIDE GFI 110 OUTLET FOR PUMP
3) SEE NOTES FROM 4/30/20 AND COMPLY
07/20/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONTRACTOR TO PAY REINSPECTION FEE FOR FAILURE TO COMPLY WITH CORRECTIONS FROM 4/30/10 INSPECTION ON THIS SHEET
2) PLEASE HAVE AN ELECTRICIAN COMPLY WITH REQUIREMENTS AND READ ALL NOTES & COMPLY
04/30/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE AN APPROVED MEANS FOR DISCONNECT FOR NEW ELECTRIC CIRCUIT FOR WATER HEATER
2) PROVIDE APPROVED CIRCUIT WIRING FOR WATER HEATER AND PUMP CIRCUITS
3) PROVIDE ACCESS TO ELECTRICAL PANEL PANEL TO VERIFY BREAKER LABELED AND CORRECT
4) INSULATION TO BE SEALED WITH ADHESIVE AND PROTECTED FROM SUN EXPOSURE
5) PANEL SUPPLY TUBING TO BE PROTECTED FROM WOOD AT ROOF LEVEL OF WATER HEATER SHED
04/27/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ACCESS TO PLAN AND PERMIT
2) NO ACCESS TO ROOF AT 10:45 AM