Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/18/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/17/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK ROOF, POLE LIGHTS AND 2ND FLOOR 2) VERIFY WIRE FILL FOR WET LOCATION WIRE NUTS 3) FINISH ARC FLASH LABELING |
|
| 11/16/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK 1ST FLOOR, EXCEPT ARC FLASH LABELING |
|
| 11/12/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) COVER OUTLET BOXES ABOVE STRIP LIGHTS 2) LIGHT FIXTURE CORD NOT ALLOWED ABOVE CEILINGS-FOLLOW MFG INSTRUCTIONS 400.7 & 8 3) NEED ARC FLASH LABELING 4) VDV CABLING HANGING OUT OF CEILING ROOM #153 |