Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T09CM03137
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2010 | ELECTRIC - UFER | Approved | IVRS - Inspection :* 1) NEED PROPER LABELING 2) INSTALL CORRISON RESISTENT SCREWS FOR STRAPPING OF EMT. |
|
| 12/30/2009 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* | |
| 12/23/2009 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1) MIN DEPTH ON PVC UNDERGROUND IS 18" TO TOP OF PVC NEC 300.5 2) CONNECT BONDING JUMPER IN GUTTER TO NEUTRAL BAR 3) OK GROUNDING ELECTRODE CONDUCTOR TAP FOR NEW 200 AMP DISCONNECT 4) INSPECTION OF UNDERGROUND AND SERVICE ONLY |
|
| 12/21/2009 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POWER DISTRIBUTION BLOCKS IN WIRING TO BE PER NEC 376.56 (B) 2) BOND SERVICE RACEWAYS AND ENCLOSURES PER NEC 250.92 3) INSTALL MAIN BONDING JUMPER IN 200 AMP SERVICE DISCONNECT 250.24 (B) 4) AVOID CREATING OBJECTIONABLE CURRENT OVER GROUNDING CONDUCTORS NEC 250.6 5) INSTALL GROUNDING ELECTRODE SYSTEM NEC 250.30 AND NEC 250 III |