Permit: T09CM03128

Parcel: 128062620


Addresses:

6062 E 21ST ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/06/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/05/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/29/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/22/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OLD METER BASE LOCKING LATCH IS BROKEN TEP WILL NEED THAT TO SEAL METER BOX
2) 100 BACK FED BREAKER REQUIRES A LOCKDOWN DEVICE, SO IT CAN'T BE REMOVED WHEN ENERGIZED
3) COOLER RECEPT IS OPEN EXPOSED WIRES, MAKE SURE IT GETS WIRE NUTED AND COVERED
4) BONDING JUMP OR TO BE A #8 CU, OR #6 AL
12/10/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE WIRE FROM WEATHERHEAD TO POWER POLE IS TOO LOW (10'0" AT WEATHER HEAD, 12'0" OVER YARD SHOULD BE)
2. MAXIMUM SIX SWITCHES TO SHUT SERV. OFF, YOU HAVE 8
3. GROUND IS SUSPECT NEED TWO GRD. RODS, WATER AND GAS BOND
4. MAKE SURE BONDING AT ISOLATED BARS IS CONNECTED TO METAL CAN
5. PIPE MAST IS LEANING SOUTH
6. ROMEX UNPROTECTED BELOW SERVICE