Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/24/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
11/23/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH PANEL DIRECTORY 2) FINISH COOLER DISCONNECTED FOR GROUNDING |
|
11/17/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) DISCONNECTING MEANS FOR EXHAUST FANS 2) FILL UNUSED OPENINGS IN FIXTURES 3) RECEPT COVERS TO BE WEATHER PROOF WEATHER OR NOT PLUGGED INTO 406.8 4) MAINTAIN WORKING CLEARANCES A/C DISCONNECTED 5) PROTECT CONDUCTOR 300.4 & IN GUTTER 6) CLEAN SURFACE UNDER LUGS 250.12 7) ONLY ONE CONDUCTOR PER TERMINAL LUG 8) TIGHTEN LOOSE FITTINGS 9) RECEIVED LETTER TO TORQUE |
|
11/15/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |