Date Description Inspector Results Comments
11/24/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK ELECTRIC
11/23/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH PANEL DIRECTORY
2) FINISH COOLER DISCONNECTED FOR GROUNDING
11/17/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) DISCONNECTING MEANS FOR EXHAUST FANS
2) FILL UNUSED OPENINGS IN FIXTURES
3) RECEPT COVERS TO BE WEATHER PROOF WEATHER OR NOT PLUGGED INTO 406.8
4) MAINTAIN WORKING CLEARANCES A/C DISCONNECTED
5) PROTECT CONDUCTOR 300.4 & IN GUTTER
6) CLEAN SURFACE UNDER LUGS 250.12
7) ONLY ONE CONDUCTOR PER TERMINAL LUG
8) TIGHTEN LOOSE FITTINGS
9) RECEIVED LETTER TO TORQUE
11/15/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*