Permit: T09CM03091

Parcel: 137055320

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T09CM03091

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
11/24/2010 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
11/15/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
WINDOW MOTORS: CORDS NOT ALLOWED IN WALL OR ABOVE CEILING 400.4 & 8, GROUND JUNCTION BOX AND CONDUCTOR COVERS TO BE PER CITY AMENDMENT 210.5 (C)
2) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20
3) PANEL SCHEDULES TO BE PER 408.4
4) WATER HEATER DISCONNECT NOT TO BE HIGHER THAN 6'-7"
5) NOTE, ON PLANS REQUIRE EQUIPMENT TO BE LISTED-VERIFY AIR CHECK MACHINES
6) INSPECTION NOT COMPLETE
11/04/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
10/19/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 2-3 1/2" PVC FROM SES TO TEP XFMR
10/14/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) PROVIDE VERIFICATION OF INSPECTION ACROSS PARKING LOT FOR PVC CONDUIT OR UNCOVER
2) NEED INFORMATION AS TO WHAT, WHERE, CIRCUIT, CONDUCTORS AND DETAIL FOR POLE BASES
10/13/2010 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE VERIFICATION OF INSPECTION ACROSS PARKING LOT FOR PVC CONDUIT OR UNCOVER
2) NEED INFORMATION AS TO WHAT, WHERE, CIRCUIT, CONDUCTORS AND DETAIL PER POLE BASES
07/21/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK PVC CONDUIT OUTSIDE WALL
2) NOTE 300.5
07/19/2010 ELECTRIC - UNDERGROUND Cancelled IVRS - RI canceled
07/09/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) CONDUIT PASSING THRU SLAB OF SERVICE AREA TO BE PER 511.4-501.10
2) OK PVC IN OFFICE AREAS UNDER SLAB