Permit: T09CM03083

Parcel: 136290570


Addresses:

7949 E MANITOBA PL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T09CM03083

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/01/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
11/25/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF WATER HEATER VENT CONNECTOR
2) DO NOT USE ANY TAPE ON VENTS
3) DO NOT USE FLEX COPPER ON WATER HEATER T & P DRAIN
4) PROVIDE A SEDIMENT TRAP IN GAS LINE AT WATER HEATER AND FURNACE
5) PROVIDE AN OVERFLOW SENSOR ON EVAP COIL
6) USE PURPLE PRIMER ON ALL PVC CONNECTIONS PRIOR TO GLUE
7) CONNECT OVERFLOW SENSOR ON CONDENSATE PUMP
8) PROVIDE PROTECTION ON REFER LINE CONNECTIONS TO EVAP. COIL FROM SCRAPING ON KNOCKOUTS
9) TIGHTEN ROMEX CONNECTORS ONTO POWER CORDS AT FURNACE
10) SECURE COPPER DRAIN LINE IN FURNACE CLOSET
11) EXTEND FURNACE VENT MINIMUM 3' ABOVE COMBUSTION AIR INTAKE
12) TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND WITH A 90 DEGREE AT END. USE A COUPLING AT SPLICE ON ROOF. SUPPORT DRAIN LINE ON ROOF AND SECURE TO SIDE OF HOUSE