Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T09CM03083
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/01/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
11/25/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF WATER HEATER VENT CONNECTOR 2) DO NOT USE ANY TAPE ON VENTS 3) DO NOT USE FLEX COPPER ON WATER HEATER T & P DRAIN 4) PROVIDE A SEDIMENT TRAP IN GAS LINE AT WATER HEATER AND FURNACE 5) PROVIDE AN OVERFLOW SENSOR ON EVAP COIL 6) USE PURPLE PRIMER ON ALL PVC CONNECTIONS PRIOR TO GLUE 7) CONNECT OVERFLOW SENSOR ON CONDENSATE PUMP 8) PROVIDE PROTECTION ON REFER LINE CONNECTIONS TO EVAP. COIL FROM SCRAPING ON KNOCKOUTS 9) TIGHTEN ROMEX CONNECTORS ONTO POWER CORDS AT FURNACE 10) SECURE COPPER DRAIN LINE IN FURNACE CLOSET 11) EXTEND FURNACE VENT MINIMUM 3' ABOVE COMBUSTION AIR INTAKE 12) TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND WITH A 90 DEGREE AT END. USE A COUPLING AT SPLICE ON ROOF. SUPPORT DRAIN LINE ON ROOF AND SECURE TO SIDE OF HOUSE |