Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/31/2009 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 12/15/2009 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1) N/H BONDS ARE LISTED FOR CAST IRON 2) JIM CAP NOT APPROVED UNDERFLOOR AND BLAKE TEE UNDER FLOOR NOT APPROVED 3) ISOLATE ABS FROM METAL STUDS 4) SUPPORT THE PIPE 5) OVERHEAD SUPPORT 6) OK TO COVER WALLS |
|
| 12/14/2009 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/11/2009 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. NOT INSTALLED PER PLAN 2. NO REDLINES ON SITE 3. MAY NOT DUMP A DRAIN INTO A VENT 4. SUPPORT ALL HORIZONTAL PIPE 5. SUPPORT ALL VERTICAL PIPE 6. TIE-WIRE NOT APPROVED STRAP 7. SUPPORT ALL STUB OUTS 8. TEST ALL NEW PIPE 9. SOFT SOLDER NOT PERMITTED UNDER SLAB 10. MAY NOT BE A COMPLETE LIST. |