Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/05/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* 1) ITEMS ON LIST OK 2) PANEL B OK |
|
| 12/31/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MANUFACTURES CLIPS TO BE EFFECTIVE-SECURELY ATTACHED 410.16 2) IF SUPPORT WIRES USED TO BE PER 300.11 CONDUIT AND FIXTURE WHIPS 3) SUPPORT VDV CABELING 725.3 & 24, 800.3 & 24 AND 300.11 4) SUPPORT M/C CABLE 12" OF BOXES AND NOT OFF OF OTHER WIRING METHODS 5) BOXES OVER FILLED 6) FILL UNUSED OPENINGS IN BOXES 7) FIXTURE WHIP NOT TO LAY ON SPRINKLER PIPING 8) BATHROOM LIGHTS NOT PER PLANS |