Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09CM03069

Parcel: 105123390


Addresses:

4133 N STONE AV


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T09CM03069

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
06/29/2010 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
06/24/2010 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) USE APPROVED ROMEX (CLAMP TYPE) CONNECTORS AT ALL ROMEX TERMINATIONS AND TRANSITION INTO RACEWAYS AND PANEL
2) PLASTIC BOXES NOT APPROVED FOR EXPOSED WORK, ROMEX NOT TO BE LEFT EXPOSED IN WALLS, NOT ALLOWED IN EXPOSED OR ACCESSIBLE CEILING AREAS PER 334
3) EQUIPMENT GROUND CONDUCTOR REQUIRED PER 250