Permit: T09CM03069

Parcel: 105123390


Addresses:

4133 N STONE AV

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
06/29/2010 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
06/24/2010 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) USE APPROVED ROMEX (CLAMP TYPE) CONNECTORS AT ALL ROMEX TERMINATIONS AND TRANSITION INTO RACEWAYS AND PANEL
2) PLASTIC BOXES NOT APPROVED FOR EXPOSED WORK, ROMEX NOT TO BE LEFT EXPOSED IN WALLS, NOT ALLOWED IN EXPOSED OR ACCESSIBLE CEILING AREAS PER 334
3) EQUIPMENT GROUND CONDUCTOR REQUIRED PER 250