Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2010 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 06/24/2010 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE APPROVED ROMEX (CLAMP TYPE) CONNECTORS AT ALL ROMEX TERMINATIONS AND TRANSITION INTO RACEWAYS AND PANEL 2) PLASTIC BOXES NOT APPROVED FOR EXPOSED WORK, ROMEX NOT TO BE LEFT EXPOSED IN WALLS, NOT ALLOWED IN EXPOSED OR ACCESSIBLE CEILING AREAS PER 334 3) EQUIPMENT GROUND CONDUCTOR REQUIRED PER 250 |