Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2010 | MECHANICAL - FINAL | Approved | CORRECTIONS HAVE BEEN MADE. | |
| 03/17/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PERMANENTLY I.D. CONDENSORS ON ROOF AND FAN COILS 2) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX 3) SUPPORT PLENIUMS AT CANVAS CONNECTORS 4) DETAILS SHOW BOTH REFER LINES BEING INSTALLED, BRAIDED CONNECTIONS AT CONDENSOR, P TRAP IN SUCTION LINE 5) PROVIDE A LETTER FROM ENGINEER IF CHANGING ANYTHING ON PLANS 6) AIR BALANCE OK |