Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - MEDICAL GAS/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2010 | PLUMBING - MEDICAL GAS/TEST | Approved | IVRS - Inspection :* | |
| 03/02/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) TESTING REQUIRES 3RD PARTY SIGN OFF, HANGERS AND LABELING OK |
|
| 02/25/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 02/05/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) AIR PIPING COMPLETE TO REMPRESOR ROOM 02,N20, AIR ALL UNDER 150 PSI TEST 2) PROVIDE A TEST ON THE ? OF VACUUM PIPING FROM 1-6-10 INSPECTION |
|
| 02/03/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) O2 AND N2O COMPLETE TO BOTTLE ROOM 2) PIPING CONTINUES FOR AIR SYSTEM |
|
| 02/02/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) O2 & N20 CONTINUES PIPING, AIR PIPING STARTER AND PURGE ON SITE |
|
| 02/01/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* O2 & N2O PIPING PROGRESSING |
|
| 01/29/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) MED GAS PIPING AND FITTINGS ON SITE, PIPING TO PROCEED 2) EQUIPMENT ON SITE |
|
| 01/11/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) SEE NOTES FROM 1/6/10 NO CHANGE |
|
| 01/06/2010 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) VACUUM UNDERGROUND TEST OK 2) AIR LOOPED TO CHAIRS TEST 150 POUND |