Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 03/16/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) A/C DISCONNECT GROUNDING, 100.3 LISTING CALLS FOR 1 WIRE PER LUG NOT 2 2) 25 & 132 BRANCH CIRCUITS GROUND WIRE CANNOT BE DOWN SIZED 3) CHECK ALL LIGHTING BOXES FOR MAKEUP AND BLANK COVERS |
|
| 03/02/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK CEILINGS 2) WILL NEED SERVICE LIGHTS AND NEED TO BE SWITCHED AT ACCESS POINT FOR AIR HANDLERS 3) NEED SERVICE RECEPTACLE ON SAME ? AS AIR HANDLERS |
|
| 02/23/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |