Permit: T09CM03047

Parcel: 12807280A


Addresses:

6275 E EASTLAND ST

Inspection Status: Approved

Inspection History: MECHANICAL - HYDRONIC PIPING

Date Description Inspector Results Comments
09/08/2010 MECHANICAL - HYDRONIC PIPING Approved IVRS - Inspection :*
09/02/2010 MECHANICAL - HYDRONIC PIPING Cancelled IVRS - RI canceled
07/15/2010 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) 100 PSI TEST ON HOT WATER HVAC PIPING OK
2) OK TO INSULATE
3) FOR FINAL PROVIDE A DUCT SMOKE DETECTOR WITH AUDIBLE AND VISIBLE ALARM FOR NEW AIR HANDLER
4) SEE ENGINEER FOR DIRECTION
5) BOILER VENT ALLOWED ONLY 1 60 DEGREE OFF SET
07/09/2010 MECHANICAL - HYDRONIC PIPING Partial Approval 1) 100 PSI TEST ON CHILLED WATER PIPING OK
2) OK TO INSULATE