Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/29/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF: 1) MAINTAIN WORKING CLEARANCES 110.26 2) BOND BUSHINGS AT DISCONNECTS 250.97 3) RECEPT COVER TO BE WEATHER PROOF OR NOT PLUGGED INTO 406.8 |
|
| 01/06/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |