Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 01/06/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE 30 AMP OVER CURRENT PROTECTION FOR 4.8 KW HEAT STRIP 2) REMOVE ALL DUCT TAPE USED OUTDOORS 3) PROVIDE UV RATED ZIP TIES OR OUTDOOR TAPE 4) SUPPORT COPPER DRAIN LINE ON ROOF EVERY 6' |