Permit: T09CM03022

Parcel: 126050320


Addresses:

4056 E SPEEDWAY BL

Inspection Status: Partial Approval

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
12/29/2010 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
12/29/2010 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
12/28/2010 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/23/2010 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) #1 FILL UNUSED OPENINGS IN TOP OF PANEL STILL HASN'T BEEN DONE
2) PANEL A TO A NIPPLE TO BE BONDED, BREAKER AND WIRES TO BE LANDED & SCREWS TO BE PUT BACK FOR BREAKER HOLDER ON PANEL
11/12/2010 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1) FILL UNUSED OPENING IN TOP OF PANEL
2) NO FUSES OR "R" PINS
3) FOR POWER TO INTERIOR NEEDS PLUGS, SWITCHES OR PLATES 8' AND BELOW
11/04/2010 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ONLY ONE CONDUCTOR PER LUG
2) REMOVE PAPER AND TIGHTEN MAIN BONDING SCREW
3) RISER HARDWARE IN BE 1/4" MINIMUM
4) WATER BOND TO BE TO INTERIOR SIDE PIPING TO BE EFFECTIVE
5) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL