Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/12/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) LABEL ALL DISCONNECTS PER 690.17 AND 705.22 2) VERIFY DERATING OF CONDUCTORS IN RACEWAY 310.15 3) RE-INSTALL SEAL TITE INTO FITTINGS 4) NEED ACCESS TO SUNNY BOY DISCONNECT 5) INSTALL ALL STRANDS UNDER TERMINAL LUGS 6) METER SOCKET LOCKED OUT CANNOT INSPECT |