Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
Permit Number - T09CM02962
Inspection Description - PLUMBING - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2010 | PLUMBING - PROGRESS | Approved | IVRS - Inspection :* | |
02/22/2010 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
02/22/2010 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :* 1) PVC INDIRECT PIPING REQUIRES PROPER INSTALLATION W/APPROVED GWF AND PRIMER, ALSO PROPER SUPPORT AND 1" MIN AG AT FS. 2) POTABLE WATER (NON CARBONATED) REQUIRES BACKFLOR PROTECTION. WILL ACCEPT APPROVED LOW HAZARD BEV PROTECTION SUCH AS DOUBLE CHOCK OR SVM CHOCK 3) SUPPORT PIPING AT BACKFLOR DS VALVE AND SUPPLY TO ICE M 4) SEAL ALL CO PLUG THREADS 5) PLAN SPECT 10 X 10 ACCESS DOOR 6) CHROME DRAIN PIPING SPECIFIES IN EXPOSED LOCATIONS. |
|
02/18/2010 | PLUMBING - PROGRESS | Not ready for Inspection | 1) INDIRECT WASTE PIPE TO BE APPROVED MATERIAL TYPE WITH FULL AIR GAP AT FLOOR SINK 2) FLOOR SINK TO BE READILY ACCESSIBLE FOR SERVICE ADN CLEANING. FLOOR SINKS REQUIRE STRAINER AND GRATE WHERE NECESSARY 3) ICE MAKER AND POTABLE WATER AT DISPENSER REQUIRES BACKFLOW PROTECTION 4) SECURE 3 CAMP SINK TO WALL 5) CAULK ALL FIXTURES 6) INSTALL COUNTER SINK CLEANOUT PLUGS WITH TAP AND LEAVE OFF FEEDER FOR INSPECTOR |
|
02/16/2010 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* |