Permit: T09CM02962

Parcel: 10511061R

Inspection Status: Approved

Inspection History: PLUMBING - PROGRESS

Permit Number - T09CM02962

Inspection Description - PLUMBING - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
02/23/2010 PLUMBING - PROGRESS Approved IVRS - Inspection :*
02/22/2010 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
02/22/2010 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
1) PVC INDIRECT PIPING REQUIRES PROPER INSTALLATION W/APPROVED GWF AND PRIMER, ALSO PROPER SUPPORT AND 1" MIN AG AT FS.
2) POTABLE WATER (NON CARBONATED) REQUIRES BACKFLOR PROTECTION. WILL ACCEPT APPROVED LOW HAZARD BEV PROTECTION SUCH AS DOUBLE CHOCK OR SVM CHOCK
3) SUPPORT PIPING AT BACKFLOR DS VALVE AND SUPPLY TO ICE M
4) SEAL ALL CO PLUG THREADS
5) PLAN SPECT 10 X 10 ACCESS DOOR
6) CHROME DRAIN PIPING SPECIFIES IN EXPOSED LOCATIONS.
02/18/2010 PLUMBING - PROGRESS Not ready for Inspection 1) INDIRECT WASTE PIPE TO BE APPROVED MATERIAL TYPE WITH FULL AIR GAP AT FLOOR SINK
2) FLOOR SINK TO BE READILY ACCESSIBLE FOR SERVICE ADN CLEANING. FLOOR SINKS REQUIRE STRAINER AND GRATE WHERE NECESSARY
3) ICE MAKER AND POTABLE WATER AT DISPENSER REQUIRES BACKFLOW PROTECTION
4) SECURE 3 CAMP SINK TO WALL
5) CAULK ALL FIXTURES
6) INSTALL COUNTER SINK CLEANOUT PLUGS WITH TAP AND LEAVE OFF FEEDER FOR INSPECTOR
02/16/2010 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*