Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM02956
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2010 | ELECTRIC - FINAL | Approved | ||
| 08/12/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/12/2010 | ELECTRIC - FINAL | Partial Approval | AFTER AN ON-SITE INSPECTION AND CAREFUL EVALUATION OF NEC ARTICLES 110, 430 AND 409 I FIND THAT THE MOTOR CONTROL CENTER MEETS CODE PROVISIONS FOR ARTICLES 430 AND 409. SPECIFICALLY THE REQUIREMENTS OF 430.102 FOR DISCONNECTING MEANS OF EACH CONTROLLER HAVE BEEN MET IN THAT EACH INDIVIDUAL CONTROLLER HAS AN INTERNAL DISCONNECT WHICH MAY BE LOCKED OUT. THE MOTOR CONTROL CENTER HAS ADDITIONAL SAFETY ENHANCEMENTS IN THE FORM OF AN EMERGENCY CUT-OFF RELAY SWITCH MOUNTED ON THE OUTSIDE OF THE CABINET. THIS KILL SWITCH ALLOWS FOR THE IMMEDIATE SHUTDOWN OF ALL THE CONTROLLERS WITHIN THE CABINET SHOULD A PHYSICAL EMERGENCY ARISE AT ANY PARTICULAR MOTOR. THERE IS STILL THE QUESTION OF THE LISTING OF THE MCC AND I AM WAITING ON SUITABLE INFORMATION FROM THE MANUFACTURER ON THE CONSTRUCTION OF THEIR CONTROL CENTER, AND HOW THEY "MIS-LABELED" THE AIC RATING OF THE EQUIPMENT. |
|
| 08/11/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MCC IS NOT LISTED 2) THERE IS NO MANUFACTURES MARKING LABEL AFFIXED TO MCC PER NEC 110.21. NUMEROUS LABELS HAVE BEEN SET TO SIGHT WITH DIFFERENT RATINGS. THERE IS NO DISCONNECTING MEANS FOR MOTRO CONTROLLERS AT MCC PER NEC 430.102 (A). NEED TO ALSO PROVIDE DISCONNECTING MEANS FOR MOTORS PER NEC 430.102 (B). DISCONNECTING MEANS FOR BOTH TO MEET REQUIREMENTS OF NEC 409 INCLUDING DISCONNECTING MEANS OF MOTORS TO MEET NEC 409.30 2) NEED TO HAVE FIELD EVALUATION FOR MCC BY NATIONALLY RECOGNIZED TESTING LAB |
|
| 08/10/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) RECALL FOR RICH JIROUDEK |