Permit: T09CM02951

Parcel: 131080780


Addresses:

5932 E 25TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/08/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
02/05/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONTRACTOR TO PAY REINSPECTION FEE FOR FAILURE TO COMPLY WITH NOTES FROM 1/14/10 INSPECTION
2) MET CULLEN O SITE, TO GO OVER REQUIREMENTS
02/04/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ACCESS AT 11:15 AM
2) FAILURE TO COMPLY WITH NOTES AND PROVIDE ACCESS WILL RESULT IN REINSPECTION FEE TO CONTRACTOR IF THIS CONTINUES
01/14/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL PER YOUR CITY APPROVED PLAN CHECK STAMPED PLAN ON SITE OR REVISE YOUR APPROVED PLAN PER YOUR INSTALLATION ON SITE
2) T & P DRAIN REQUIRES 90 DEGREE DOWN
3) DRAIN BACK, SHOULD DRAIN BACK FROM PANEL TANK
4) ELECTRICAL CIRCUITS TO MEET 2006 NEC REQUIREMENTS