Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T09CM02950
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/29/2009 | BUILDING - FINAL | Approved | IVRS - Inspection :* 1) PER APPROVED PLANS |
|
12/22/2009 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CONTINUED NOT READYS WILL RESULT IN REINSPECTION FEE |
|
12/11/2009 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
11/24/2009 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE APPROVED SUPPORT ON ROOF FOR PIPING AND PANEL MINIMUM 1 1/2" ABOVE ROOF SURFACE 2) PROVIDE A SITE SPECIFIC PLAN FOR THIS SYSTEM 3) WATER HEATER IS ELEVATED ON A FEILD BUILT PLATFORM IN A MOBILE HOME. PROVIDE AN APPROVED PLAN FOR STRUCTURAL SUPPORT FOR THIS WEIGHT IN EXCESS OF 450 POUNDS 4) SEAL ALL PIPE PENETRATIONS INTO STRUCTURE 5) VERIFY WIRE SIZE AND CIRCUIT BREAKER ARE COMPATIBLE WITH 25 AMP 120 VOLT CIRCUIT (20 AMP BREAKER INSTALLED) POSSIBLE NUSICENCE TRIPPING OF BREAKER 6) PROVIDE CORRECT ROOF JACK FOR TEMPERATURE PROBE AND CONDUIT WITH SEAL OFF 7) MAKE WEATHER TIGHT ALL OLD AND NEW PENETRATIONS |
|
11/16/2009 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) HAVE ALL PARTIES ON SITE FOR INSPECTION |
|
11/13/2009 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO ONE AT HOME, UNABLE TO DO INSPECTION 11:35 AM 2) HAVE PERMITS AND INSTALLATION PAPERWORK ON SITE |