Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/04/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BREAKER TO BE LISTED FOR USE BY MANUFACTURE 2) NM CABLING UNDER TRAILER TO BE IN AN APPROVED RACEWAY AND SUPPORTED 3) CORRECTLY IDENTIFY UNDGROUNDED CONDUCTORS 4) BOND JUNCTION BOX 5) PLEASE VERIFY SWITCH IS 30 AMP RATED 6) CLEARLY IDENTIFY CIRCUITS |