Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T09CM02936
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/08/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 01/11/2010 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CW TOUCHING METAL COMBUSTION AIR OPENING 2) ISOLATE AND SECURE TUBING, INCLUDING T & P DRAIN PIPE. CORRECT SLOPE OF T & P PIPING AT CONNECTION TO EXISTING 3) REPAIR PIPE INSULATION WHERE DAMAGED |
|
| 11/16/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |