Permit: T09CM02919

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM02919

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/14/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/30/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) TIGHTEN GROUNDED TERMINATIONS
2) IDENTIFY GROUNDING CONDUCTOR AT LUGS
3) PLANS CALL FOR CT CABINET-ALL WE HAVE IS A JUNCTION BOX
4) PLEASE VERIFY IF SWITCH IS TO BE FUSED OR NON FUSED
5) FIRE STOPPING BETWEEN LEVELS NEEDED
03/24/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) METERING EQUIPMENT NOT INSTALLED YET