Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM02919
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/14/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/30/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) TIGHTEN GROUNDED TERMINATIONS 2) IDENTIFY GROUNDING CONDUCTOR AT LUGS 3) PLANS CALL FOR CT CABINET-ALL WE HAVE IS A JUNCTION BOX 4) PLEASE VERIFY IF SWITCH IS TO BE FUSED OR NON FUSED 5) FIRE STOPPING BETWEEN LEVELS NEEDED |
|
03/24/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) METERING EQUIPMENT NOT INSTALLED YET |