Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T09CM02908
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 12/03/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* EXTERIOR ELECTRICAL OUTLETS REQUIRE GFCI PROTECTION. DID YOU OBTAIN AN ELECTRICAL WIRING PERMIT AND HAVE THIS NEW ELECTRICAL WIRING INSPECTED. AN IRON PIPE THREAD CAP IS NOT APPROPRIATE FOR A FLARED FLEX ADAPTOR. CAP PIPING AS PREVIOUSLY NOTED. T&P PIPING SHOULD ALSO BE CAPPED. NEW HEAT PUMP REQUIRES PERMIT AND INSPECTIONS |
|
| 11/30/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PERMANENTLY CAP OLD WATER HEATER GAS PIPING 2) SECURE THE WEATHER PROOF ENCLOSURE TO STRUCTURE 3) PLEASE READ AND PROVIDE INSTALLATION INSTRUCTIONS FOR INSULATION BEING USED, MOST ARMAFLEX STYLE INSULATION REQUIRE PROTECTION FROM SUN EXPOSURE WITH A TYPE OF PAINT MATERIAL FROM MANUFACTURE |