Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T09CM02904

Parcel: 10712226B


Addresses:

2831 N STONE AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/20/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
04/14/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
04/13/2010 PLUMBING - FINAL Cancelled IVRS - RI canceled
03/19/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
03/03/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SUBJECT TO REVISED APPROVED PLAN SHOWING ADDITIONAL HAND SINK
2) P-4 REQUIRES A GRATE
3) RE-READ FIXTURE SPECS ON P-2 HAND SINK P-1
4) RE-READ FIXTURE SPECS ON P-4 FLOOR SINK-REQUIRES TRAP PRIMER
5) INSTALL ICE MAKER
AT 3 COMP SINK:
A) EACH FIXTURE TRAP TO HAVE A VENT DOWNSTREAM
B) FITTINGS BELOW THE FLOOD RIM TO BE DRAINGE TYPE
C) A SAN TEE MAY NOT BE INSTALLED OK ITS BACK
D) FLOW CONTROL TO BE INSTALLED WITH OUTLET AT THE TOP
E) A N/H BAND IS LISTED FOR CAST IRON-USE APPROVED COUPLING
F) PROVIDE ESCUTENEON PLATES AT WALL
G) AIR GAPS STRICTLY ENFORCED
7) PROVIDE STERILIZATION REPORT
8) PROVIDE CLEAN BACTERIA REPORT
9) PROVIDE BACKFLOW CERT
10) RECONNECT MOP SINK VENT AT STAIRWELL
11) INSTALL MIXING VALVE PER DETAIL ON P-2
12) MODIFY WATER HEATER TO COMPLY WITH DETAIL ON P-2