Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 04/14/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/13/2010 | PLUMBING - FINAL | Cancelled | IVRS - RI canceled | |
| 03/19/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/03/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SUBJECT TO REVISED APPROVED PLAN SHOWING ADDITIONAL HAND SINK 2) P-4 REQUIRES A GRATE 3) RE-READ FIXTURE SPECS ON P-2 HAND SINK P-1 4) RE-READ FIXTURE SPECS ON P-4 FLOOR SINK-REQUIRES TRAP PRIMER 5) INSTALL ICE MAKER AT 3 COMP SINK: A) EACH FIXTURE TRAP TO HAVE A VENT DOWNSTREAM B) FITTINGS BELOW THE FLOOD RIM TO BE DRAINGE TYPE C) A SAN TEE MAY NOT BE INSTALLED OK ITS BACK D) FLOW CONTROL TO BE INSTALLED WITH OUTLET AT THE TOP E) A N/H BAND IS LISTED FOR CAST IRON-USE APPROVED COUPLING F) PROVIDE ESCUTENEON PLATES AT WALL G) AIR GAPS STRICTLY ENFORCED 7) PROVIDE STERILIZATION REPORT 8) PROVIDE CLEAN BACTERIA REPORT 9) PROVIDE BACKFLOW CERT 10) RECONNECT MOP SINK VENT AT STAIRWELL 11) INSTALL MIXING VALVE PER DETAIL ON P-2 12) MODIFY WATER HEATER TO COMPLY WITH DETAIL ON P-2 |