Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2010 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 01/11/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) OK SERVICE EQUIP-SUBJECT TO WORKING CLEARANCE ISSUES TO BE RESOLVED BETWEEN OWNER OF THIS PROPERTY AND PROPERTY NORTH OF THIS 2) OK TO CLEAR SERVICE WHEN RESOLVED |
|
| 01/08/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CALLED & LEFT MESSAGE PER REQUEST 2. CONTRACTOR NEEDS TO BE ON SITE TO OPEN EQUIPMENT 3. SEE NOTES ON PREVIOUS INSPECTION. 4.BE ADVISED THAT DUE TO CONSTRUCTION OF GRADE AT PROJECT NORTH OF THIS BUILDING THERE WILL BE WORKING CLEARANCE ISSUES IN FRONT OF NEW SERVICE, SEE SEC 110-26 NEC NEED TO VERIFY WATER & GAS BONDING |
|
| 01/06/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COULD NOT LOCATE REVISED PLANS 2) NEED TO COMPLETE PREVIOUS INSPECTION ITEMS 3) HAVE PARALLEL NEUTRAL PATHS |
|
| 12/30/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE NOT PER PLAN, REVISE PLAN, CHECK GROUND AND SUPPLY SIDE OF DISCONNECTS PER 250.66, 250.92 AND 250.102 C |