Permit: T09CM02892

Parcel: 133411070


Addresses:

9666 E 3RD ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
12/18/2009 BUILDING - FINAL Approved IVRS - Inspection :*
12/04/2009 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE AN ELECTRICAL PERMIT FOR THE NEW WIRING. ORIGINAL WATER HEATER WAS GAS
2) ALL SUPPORTS REQUIRED TO BE TREATED, REDWOOD OR OTHER WEATHER RESISTANT SUPPORTS
3) FLASHING REQUIRED AT SVOE PENETRATION
4) PROVIDE SAFE ACCESS TO ROOF
5) IS THERE PROPER ISOLATION BETWEEN METAL AND COPPER AT ROOF PENETRATION ?
6) ISOLATE AND SECURE T & P DRAIN LINE TOUCHING METAL