Permit: T09CM02868

Parcel: 12510006B


Addresses:

3595 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T09CM02868

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/14/2010 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/08/2010 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. HAVE OPEN JUNCTION BOXES. CONTRACTOR IN PROCESS OF PULLING HOME RUNS
2. STRAP MC CABLE WITHIN 12" OF BOXES
3. REMOVE TEMPORARY LIGHTING
4. ENSURE ELECTRICAL CONTRACTOR IS READY FOR INSPECTION PRIOR TO SCHEDULING. NEED TO HAVE CEILINGS OPEN FOR INSPECTION
12/09/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SOUTH CASH REGISTER UNDERGROUND, SHELF LIGHTING, BABY WRAP STATION NORTH CASH REGISTER UNDERGROUND ALL OK