Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T09CM02808
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/20/2010 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/18/2010 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : 1. PROVIDE MECHANICAL COLLARS ON EXHAUST DUCT SPLICES. 2. PROVIDE DUCT SIZES AS SHOWN ON PLANS 3. DUCT NOT PROPERLY INSULATED 4. DRYER VENT IS RUNNING IN THE WRONG DIRECTION 5. PROVIDE R-8 INSULATION ON DUCT IN VENTED ATTIC. 6. ALL PVC TO HAVE JOINTS PRIMERED PRIOR TO GLUE, PRIMER IS TO BE PURPLE IN COLOR PER UPC 7. PROVIDE DATA ON BUBBLE INSULATION 8. PROVIDE FULL RADIUS BENDS ON ALL FLEX DUCTS 9. LINE SETS NOT PROPERLY INSULATED 10. DRYER VENT NOT TO EXCEED 25' (DEDUCT 5' PER 90 DEGREE BEND). |