Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T09CM02808
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/19/2010 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
07/16/2010 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CLOSET FLANGES ARE TO SIT ON TOP OF FINISHED FLOOR AND EXTEND 1/4" ABOVE FINISHED FLOOR 2) SOLDER 90 DEGREE ELL ON T & P RELIEF DRAIN TERMINUS 3) SET AND HOOK UP DISHWASHERS PRIOR TO FINAL 4) HAVE STERILIZATION AND CLEAN BACTERIA REPORTS |
|
05/21/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CORRECTIONS MADE OK 2) STILL NEED TO SEE CLOSET FLANGES |
|
05/20/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) WATER TEST DOWN 2) TUB LEAKING 3) BACK PITCHED SECITONS NOT PERMITTED |
|
05/18/2010 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. NO TEST ON ABS 2. ABS SHALL BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION, AND AT TEH ENDS OF BRANCHES; THEN, NO MORE THAN FOUR FEET BETWEEN HANGERS. VERTICALLY, PIPING SHALL BE SUPPORTED AT EACH FLOOR WITH MID STORY GUIDES. 3. VENTS SHALL BE INSTALLED LEVEL, OR SO DESIGNED TO DRAIN BACK TO THE FIXTURE SERVED. 4. DRAINAGE PIPING TO BE INSTALLED AT 2% PITCH 5. SHOWER PAN AND TUBS TO BE TESTED. 6. WILL RECHECK CLOSET FLANGES AFTER SUB FLOOR IS INSTALLED. |