Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/19/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ROUGH ELECTRIC, NO UFER |
|
| 05/18/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. UFER NOT INSTALLED - REQUIRED PER 250.50 2. HAVE BUILDING INSPECTOR VERIFY FIRE WALL PENETRATIONS 3. INSTALL & SUPPORT VDV CABLING AS PER 725.24 & 800.24 |