Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM02801
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/17/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CONTRACTOR CANCELLED PER M. HENSON |
|
12/15/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED CITY STAMP ON REVISIONS |
|
12/14/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
12/11/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
12/10/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) FIXTURE "F" & "E" NOT AS PER PLANS-TYPE AND IEC. LOAD CALCULATION 2) SEAL RACEWAYS TO WALK IN BOXES 200.7 ROOF: 1) CORDS NOT ALLOWED FOR PERMANENT WIRING 2) AREAS OCCUPIED WITHOUT INSPECTION CLEARNACES |