Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/24/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BALANCE REPORT NOT COMPLETE 2) INCLUDE OUTSIDE AIR VENTS AND MAKE UP AIR UNIT 3) NEED TO TEST HEAT SENSOR 4) DO NOT USE JB WELD TO FASTEN HINGES TO EXHAUST FAN 5) PROVDIE A GREASE RECEPTOR AT ? 6) PROVIDE A GASKET UNDER FAN 7) EXTEND SEWER VENTS 2' ABOVE FRESH AIR INTAKE AND MAKE UP AIR UNIT 8) PROVIDE AN APPROVED CAP ON WATER HEATER VENT |
|
| 10/17/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |