Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T09CM02800
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2011 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/17/2011 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) DOORS LOCKED AND NO ACCESS |
|
| 08/18/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CHECKED 1ST LAYER OF FIRE WRAP AND 2ND LAYER OF UPPER SECTION-OK TO COMPLETE FIRE WRAP 2) FOR FINAL YOU WILL NEED A HEAT SENSOR, AIR BALANCE REPORT ON HOOD, OUTSIDE AIR ON A/C UNITS, CAPTURE & CONTAINMENT AND HINGE KIT ON FAN 3) WHY IS THE WATER HEATER VENTING COVERED WITH FOIL TAPE ? 4) REMOVE ALL OF THE TAPE AND REPAIR VENT AS NEEDED |
|
| 08/03/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CHECKED WELDS ON GREASE DUCT 2) OK FOR 1ST LAYER OF FIRE WRAP AND 2ND LAYER ON UPPER 3' OF DUCT ONLY |