Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T09CM02800

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/24/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
10/17/2011 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
There is no access to the site.| 920*
1) DOORS LOCKED AND NO ACCESS
08/18/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CHECKED 1ST LAYER OF FIRE WRAP AND 2ND LAYER OF UPPER SECTION-OK TO COMPLETE FIRE WRAP
2) FOR FINAL YOU WILL NEED A HEAT SENSOR, AIR BALANCE REPORT ON HOOD, OUTSIDE AIR ON A/C UNITS, CAPTURE & CONTAINMENT AND HINGE KIT ON FAN
3) WHY IS THE WATER HEATER VENTING COVERED WITH FOIL TAPE ?
4) REMOVE ALL OF THE TAPE AND REPAIR VENT AS NEEDED
08/03/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CHECKED WELDS ON GREASE DUCT
2) OK FOR 1ST LAYER OF FIRE WRAP AND 2ND LAYER ON UPPER 3' OF DUCT ONLY