Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T09CM02792
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2009 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
11/13/2009 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WEST WALL GARAGE (SMALL SECTION OF LEDGER NOT NAILED TO STUDS) 2) SHIM ALL 3 PT BEARING, REAR WALL (DIAGONAL) AND CENTER BEARING WALLS, SEE TRUSS DRAWINGS OR LOOK FOR RED PAINT ON BOTTOM CHORDS 3) AT REAR SLIDING DOOR DETAIL 14/DT1 REQUIRED, BLOCK PANELS 4) AT CONNECTION ROOF TO ALL BLOCKED PANELS, END NAIL USE NAILS LONG ENOUGH SO THAT THE PENETRATION CAN BE SEEN FROM BELOW 5) PLEASE LEAVE YOUR T.J. PLAN ON SITE 6) PAGE SD2,NAILING YOU USED STAPLES, NAIL AT 3" AND 6" (NAIL ALL LEDGERS) |